Sabotage-proof RC 2 emergency generator 41 kVA with internal automatic
emergency power 72 hours with Yanmar engine 4 TNV 98 for mains
parallel operation
Aggregate type: stationary
Design: Super soundproofed
Technical data engine:
Engine Manufacturer: Yanmar
Engine Model: 4 TNV 98
Engine No.: in production
Motor power: 37.7 KW electronically controlled
Cooling: Water-cooled
Tempering: Electric 12 V DC
Speed: 1500 rpm
Fuel: Fuel oil EN 590 and diesel B7
Technical data generator:
Generator manufacturer: Mecc Alte
Generator type: Sychron with AVR
Gene. No.: in production
Generator power: 45 kVA
Voltage: 400 / 231 volts
Power factor: cos. - PHI 0.8
Speed: 1500 rpm
Switchgear:
Version: Automatic start
Functions: Emergency power operation with ÜSY
Tank:
Design: Base frame tank with drip pan
Capacity / litre: 990
Scope of delivery:
Design: Weatherproof, RAL 7046 (telegrau 2) soundproofed version
essentially consisting of:
Our LZPD series was developed by us for the North Rhine-Westphalia
State Police. Essentially, digital radio sites are supplied with
backup power from the grid. Since some sites are very remote, special
attention was paid to the monitoring of the plant and sabotage
security. All doors have a 2-fold drive rod lock and can be adapted to
the customer's own locking system with profile half cylinders 30/10
(not included).
The thermostatically heated system is equipped with a drip pan with
optional leakage monitoring. The A51268 tank system is sufficient for
at least 204 hours with 50% load. In full load operation, 109 hours
are possible. The requirement of 72 hours is thus clearly exceeded.
The emergency power system is designed for fully automatic emergency
power operation. In automatic mode, the unit is started immediately in
the event of a power failure. When the nominal frequency and nominal
voltage are reached, the mains contactor is switched off and the
generator contactor is switched on within approx. 15 seconds. After
the network is restored, the automatic uninterruptible switch back to
mains operation takes place after the network has been checked
(approx. 180 seconds).