Emergency current aggregates WA NOTSTROMTECHNIK WA-V 250 S

energy & engines: power generators, engines, turbines, boilers / power generators / Emergency current aggregates

logo dealer

Aggregatebau WA Notstromtechnik GmbH
[ dealer profile ]

Mr Marcus Kleine-Wienker
Waldstr. 11
33415 Verl
Germany

  • +49 (0)52... phone

approved
dealer
verified user

RESALE member since 2004

  • machine list (65)
item-No.: 161603642 Quantity: 1 Date: 04.03.2024
Year of manufacture: 2023 new machine Location: Land-de Germany 33415 Verl
Price:
Manufacturer: WA NOTSTROMTECHNIK
Model: WA-V 250 S
Type of machine: Emergency current aggregates
Description: Emergency current aggregates WA NOTSTROMTECHNIK WA-V 250 S

new machine

Execution:

Aggregate type:
stationary

Execution:
Soundproofed

Technical data engine:

Engine manufacturer:
Volvo

Engine:
TAD841GE

Engine No.:
3008598229

Power:
254 KW

Cooling:
Water-cooled

Occasion:
Electric 24 V DC

Speed:
1500 rpm

Fuel:
Fuel oil EN 590

Technical data generator:

Generator manufacturer:
Stamford

Generator type:
UCDI274K

Gene. No.:
N22E211704

Generator power:
250 kVA

Voltage:
400 / 231 Volt

Power factor:
Cos. - PHI 0.8

Speed:
1500 rpm

Switchgear:

Execution:
Automatic start

Functions:
Parallel operation

Switch:
Generator switch 4 poles

Delivery:
Built

Tank:

Execution:
Base frame tank with drip pan

Content / liter:
990

Dimensions of the power unit:

Width approx. mm:
1,200 mm

Height approx. mm:
2.291 mm

Length approx. mm:
3,640 mm

Weight approx. KG:
3.320

Condition:
New

Year of construction:
2023

Delivery period:
Instant Verl

Hours:
0

Location:
Verl - Germany

Scope of delivery:
Emergency power generator super-soundproofed with approx. 66 db"A" measured in 7 meters with an all-round measurement in 7 meters at 7 measuring points as a backup power system Type: WA V 250 "S"

Other features:

Fuel tank capacity 1100 litres
Oil drip pan in the base frame
electronic speed controller
Sturdy additional base frame with forklift pockets

Automatic start with IG 200 control

Internal emergency power switchgear 4 pole - generator switch 400 A4468 amps

Function: In the event of a power failure, the start command is transferred to the diesel generator. When the nominal speed and nominal voltage are reached, the generator switch is switched on. In the event of a return to the mains, the automatic system monitors the mains voltage. When this is stable again, the switch back to mains operation takes place WITHOUT INTERRUPTION. The diesel generator is stopped after the cooling time and waits in automatic mode for the next power failure.

Power switch with motor support is required on site.

The emergency power system as a backup power system is ready for operation and available from the Verl warehouse.
seller offer No. resale 1358
Machine in stock: Yes
Seller-item-No.: 1358
Share this machine on Facebook:

Inquiry

Machinery dealer?

Please remit optionally

Send wanted inquiry?

(to all dealers for such a machine)

Copy to you?

(copy of your inquiry will be sent to your email address)

Save input data

(Save input data for further inquiries)

more WA Notstromtechnik WA-V 250 S + similar WA Notstromtechnik-Model

WA NOTSTROMTECHNIKWA I 250 S
2023 WA NOTSTROMTECHNIKWA-DG 250 S
WA NOTSTROMTECHNIKWA-Y 40 S Stationary
WA NOTSTROMTECHNIKWA-Y 15 S Stationary
WA NOTSTROMTECHNIKWA D 30 S Stone
2023 WA NOTSTROMTECHNIKWA-I 100 S Stage V
2023 WA NOTSTROMTECHNIKWA-YG 50 S Stage V
2023 WA NOTSTROMTECHNIKWA-S 550 S Stage V
2023 WA NOTSTROMTECHNIKWA-D 100 S Stage V
2023 WA NOTSTROMTECHNIKWA-I 85 S Stage V