Execution:
Aggregate type: stationary
Design: Soundproofed
Technical data engine:
Engine manufacturer: Deutz
Engine type: F 4 M 2011
Motor power: 27 KW
Cooling: Oil-cooled
Start: Electric 12 V DC
Speed: 1500 rpm
Fuel: Heating oil EN 590
Technical data generator:
Generator manufacturer: Stamford AvK
Generator Type: Synchronous
Generator power: 30 kVA
Voltage: 400 / 231 Volt
Power factor: cos. - phi 0.8
Speed: 1500 rpm
Switchgear:
Execution:
Automatic start
Functions: Remote start
Switch: Generator switch 4 pole
Delivery: Assembled
Tank: Version:
Base frame tank with drip tray
Content / Litre: 50
Dimensions of the unit:
Width approx. mm: 960
Height approx. mm: 1,236
Length approx. mm: 2,000
Weight approx. KG: 1.075
Use:
Bearing number: 1229
Condition: Demonstration machine
Year of construction: 2022
Delivery time: immediately Verl
Operating hours: 2
Location: Verl - Germany
Scope of delivery:
Emergency power generator as emergency power supply system for the
emergency power supply as a backup power system with an original Deutz
industrial diesel engine with speed control and Stamford three-phase
synchronous generator. The motor and generator are elastically mounted
on a common runner frame. Installed in a modular sound insulation
encapsulation.
Powder coated in RAL 3000
Other additional features:
Tank capacity 50 litres, refuelling directly at the tank
2.14 liters / hour at 25 % load
4.07 liters / hour at 50 % load
5.46 liters / hour at 75% load
7.18 liters / hour at 100% load
Internal start-stop automatic (type: AMF DSE 4150) with display of all
important motor and generator messages. Functional display digitally
on the display. Generator switch 40 Ampere 4 poles integrated on the
generator (generator). Internal A51268 battery charger 230 Volt –
12 Volt DC
Optionally available at an additional cost:
Automatic start with mains & generator switching 4 poles
External emergency power switchgear for installation in the building
and 4-pole mains generator switching
Function: In the event of a power failure, the start command is
transferred to the diesel engine. When the rated speed and nominal
voltage are reached, the generator switch is switched on. When the
grid is reversed, the automatic monitors the mains voltage. If this is
stable again, the switch back to mains operation takes place. The
diesel engine is stopped after the cooling time and waits in automatic
mode for the next power failure.
The emergency power system as an emergency power supply is ready for
operation and immediately available from stock Verl.