Skip to content

WA Notstromtechnik WA Y 45 S RC 2 Standby power systems

GermanyID 162153825

GermanyID 162153825

New machineVerified seller
Request price Directly to the seller

Technical data

· ID 162153825
Source: seller information

Standby power systems

Condition
New machine
Location
33415 Verl

Identifikation

ManufacturerWA Notstromtechnik
ModelWA Y 45 S RC 2
Item number1381

Technik

Quantity1

Description

Sabotage-proof RC 2 emergency generator 41 kVA with internal automatic emergency power 72 hours with Yanmar engine 4 TNV 98 for mains parallel operation

Aggregate type: stationary

Design: Super soundproofed

Technical data engine:

Engine Manufacturer: Yanmar

Engine Model: 4 TNV 98

Engine No.: in production

Motor power: 37.7 KW electronically controlled

Cooling: Water-cooled

Tempering: Electric 12 V DC

Speed: 1500 rpm

Fuel: Fuel oil EN 590 and diesel B7

Technical data generator:

Generator manufacturer: Mecc Alte

Generator type: Sychron with AVR

Gene. No.: in production

Generator power: 45 kVA

Voltage: 400 / 231 volts

Power factor: cos. - PHI 0.8

Speed: 1500 rpm

Switchgear:

Version: Automatic start

Functions: Emergency power operation with ÜSY

Tank:

Design: Base frame tank with drip pan

Capacity / litre: 990

Scope of delivery:

Design: Weatherproof, RAL 7046 (telegrau 2) soundproofed version essentially consisting of:

Our LZPD series was developed by us for the North Rhine-Westphalia State Police. Essentially, digital radio sites are supplied with backup power from the grid. Since some sites are very remote, special attention was paid to the monitoring of the plant and sabotage security. All doors have a 2-fold drive rod lock and can be adapted to the customer's own locking system with profile half cylinders 30/10 (not included).

The thermostatically heated system is equipped with a drip pan with optional leakage monitoring. The tank system is sufficient for at least 204 hours with 50% load. In full load operation, 109 hours are possible. The requirement of 72 hours is thus clearly exceeded.

The emergency power system is designed for fully automatic emergency power operation. In automatic mode, the unit is started immediately in the event of a power failure. When the nominal frequency and nominal voltage are reached, the mains contactor is switched off and the generator contactor is switched on within approx. 15 seconds. After the network is restored, the automatic uninterruptible switch back to mains operation takes place after the network has been checked (approx. 180 seconds).

Inquire about this machine

Your inquiry goes directly to the seller of this machine.

Fields marked with an asterisk are required.

An amount is optional. In the “Send price proposal” dialog you can also send your proposal as a message only.
Further details (optional)
Note on “Save details for 30 days”
Your contact details (title, name, email, phone, company, street, postcode, town, country and the “dealer” indication) are stored in cookies in this browser for 30 days so that the form is already filled in for your next inquiry. If you untick the box and send an inquiry, the stored details will be deleted.

When you submit, your inquiry is forwarded to the seller. More information can be found in our privacy notice.

Similar machines

Inquiry about WA Notstromtechnik WA Y 45 S RC 2 Standby power systems

ID: 162153825