발전소 - Complete POWER PLANT 10 MW / 2 MW

발전기엔진터빈보일러 / 발전기

For Sale: Complete 10 MW / 2 MW Cogeneration Power Plant Available for immediate acquisition: a fully integrated power plant for the combined and efficient production of heat and electricity through a cogeneration system. Technical Description: The whole installation (Model: E.V.A.) for sale ...

생산자: -

모델:Complete POWER PLANT 10 MW / 2 MW

기계의 유형: 발전소

품목 아니오.: 167412860

양: 1

날짜: 03.06.2026

제조 연도: 2009

위치: Poland

값:


Seller-item-No.:7534977

For Sale: Complete 10 MW / 2 MW Cogeneration Power Plant

Available for immediate acquisition: a fully integrated power plant for the combined and efficient production of heat and electricity through a cogeneration system.

Technical Description:

The whole installation (Model: E.V.A.) for sale includes components listed below:

STEAM BOILER

Manufacturer: Wehrle Werk

Year: 1999,

Heating capacity: up to 10 MW

Fuel type: biomass/RDF

Fuel gas volume: 20.000 Nm³/h

Fuel consumption: approx. 2500 kg/h

Fuel need: approx. 20 000 t/a

Average combustion temperature: approx. 900°C

Main steam pressure: water steam with 40 bar

Main steam temperature: 410°C

Main steam mass flow: 11 t/h

Combustion power gross: max. 10.000 kW

Combustion power gross: min. 7000 kW

Water content: 25 m³

STEAM TURBINE

Manufacturer: KKK / Siemens SST110

Electrical capacity: up to 2 MW

Year: 1999, serial number 4.746.114

Type: TWIN steam turbine used as condensation machine AFA4 / AFA6 GTA electrohydr.

Turbine control (Kuhse with Siemens S5), AFA 4: drive speed: 1500 1/min, rapidlocking

Speed min: 1678 1/min,

Speed max: 1712 1/min

Gear ratio: 11.96:1

Live steam pressure: min. 31 bar – max. 47 bar

Live steam temperature: min. 350°C – max. 428°C

Waste steam pressure: min. 0.50 bar – max. 2.50 bar, in operation 1.50 bar

Waste steam temperature: 347°C; AFA 6: drive speed 1500 1/min

AND ALL OTHER COMPONENTS NECESSARY TO BUILD THE COMPLETE POWER PLANT!

Such as:

- Sterling water feed pumps
- Boiler water system from Hager & Elsässer with softening installation and reverse osmosis unit
- Horizontal superheater
- Economizers
- Reduction station
- Cooling station
- Water treatment plant
- Fuel feeding system
- Air protection devices with bag filters
- Chimney 33 m high – located inside the boiler room (above the roof of 17 m), which discharges exhaust gases and auxiliary facilities, mainly connected with fuel storage
- And many others

Ready to build in a new location NOW!

Available now!

The installation was built in Germany, where it worked on RDF fuel.

Then, sold and transported to Poland (current location).

Find more here - /

Contact us at -
페이스 북에서이 컴퓨터를 공유 :

문의

기계 딜러?

선택적으로 송금하십시오.

원하는 문의를 보내시겠습니까?

당신에게 복사?

Save input data

For Sale: Complete 10 MW / 2 MW Cogeneration Power Plant

Available for immediate acquisition: a fully integrated power plant for the combined and efficient production of heat and electricity through a cogeneration system.

Technical Description:

The whole installation (Model: E.V.A.) for sale includes components listed below:

STEAM BOILER

Manufacturer: Wehrle Werk

Year: 1999,

Heating capacity: up to 10 MW

Fuel type: biomass/RDF

Fuel gas volume: 20.000 Nm³/h

Fuel consumption: approx. 2500 kg/h

Fuel need: approx. 20 000 t/a

Average combustion temperature: approx. 900°C

Main steam pressure: water steam with 40 bar

Main steam temperature: 410°C

Main steam mass flow: 11 t/h

Combustion power gross: max. 10.000 kW

Combustion power gross: min. 7000 kW

Water content: 25 m³

STEAM TURBINE

Manufacturer: KKK / Siemens SST110

Electrical capacity: up to 2 MW

Year: 1999, serial number 4.746.114

Type: TWIN steam turbine used as condensation machine AFA4 / AFA6 GTA electrohydr.

Turbine control (Kuhse with Siemens S5), AFA 4: drive speed: 1500 1/min, rapidlocking

Speed min: 1678 1/min,

Speed max: 1712 1/min

Gear ratio: 11.96:1

Live steam pressure: min. 31 bar – max. 47 bar

Live steam temperature: min. 350°C – max. 428°C

Waste steam pressure: min. 0.50 bar – max. 2.50 bar, in operation 1.50 bar

Waste steam temperature: 347°C; AFA 6: drive speed 1500 1/min

AND ALL OTHER COMPONENTS NECESSARY TO BUILD THE COMPLETE POWER PLANT!

Such as:

- Sterling water feed pumps
- Boiler water system from Hager & Elsässer with softening installation and reverse osmosis unit
- Horizontal superheater
- Economizers
- Reduction station
- Cooling station
- Water treatment plant
- Fuel feeding system
- Air protection devices with bag filters
- Chimney 33 m high – located inside the boiler room (above the roof of 17 m), which discharges exhaust gases and auxiliary facilities, mainly connected with fuel storage
- And many others

Ready to build in a new location NOW!

Available now!

The installation was built in Germany, where it worked on RDF fuel.

Then, sold and transported to Poland (current location).

Find more here - /

Contact us at -
seller offer No. resale 7534977
페이스 북에서이 컴퓨터를 공유 :

파는 사람

logo dealer

UCY Industrial GmbH

Mr Nick Breinfalk
82049 Pullach
Germany

RESALE 구성원 이래 2024

  • 컴퓨터 목록 (1446)

문의

기계 딜러?

선택적으로 송금하십시오.

원하는 문의를 보내시겠습니까?

(그러한 기계에 대한 모든 딜러에게)

당신에게 복사?

(귀하의 문의 사본이 귀하의 이메일 주소로 발송됩니다)

Save input data

(Save input data for further inquiries)

감시 목록에 추가